PROJECT CASE STUDY
·
#631210
Glycol Removal and Water Flush on Closed Cooling Water System
FINAL
Glycol Concentration: Approximately 1%
SNAPSHOT
ASSET(S)
Closed Cooling Water System
YEAR
2026
OBJECTIVE
WHAT WE FOUND
HOW WE DID IT
PROCESS
Stage equipment, confirm tie-in points, and review site safety requirements.
Drain glycol from the system and its 16 underground low points.
Flush with clean water to dilute and remove remaining glycol.
Complete a second rinse to address crystallization.
Sample the low points with a refractometer and turn the system over for customer refill.
TECHNICAL DETAILS
VERIFICATION METHOD
Low-Point Sampling with a Temperature-Compensated Glycol Refractometer
FLUID
Glycol and Water Mixture
FLUID VOLUME
41,090 Gallons Recovered
RELEVANT SPECIFICATIONS
16 underground low points, approximately 9 feet deep. Two water rinses were completed.
THE NUMBERS
Glycol Concentration
Approximately 10%
→
Approximately 1%
SAFETY
100% Safety Performance
Every Step. Every Reading.
This page is the short version. The full report walks through every step we took, how we verified it, and what the numbers came back at. Customer details are redacted. The data isn’t.
Download Full Technical Report